Main Performance Characteristics 2)


TECHNICAL DATA
RATING
 
A0 - A30
A60
H0 - H120
J0 - J60
Weight Complete Wall System (kg/m2)1)
26.2
32
49.2
49.2
Weighted sound reduction index Rw(dB)
36
38
50
50
Integrity & Stability steel (minutes)
60
60
120
120
Thermal insulation (minutes)
0 / 30
60
120
0 / 60
Dimension W (mm)
130
130
180
180
Dimension D (mm)
38
38
38
38
1) Spans up to 4.5 m, depending on windload.
Sheet thickness internal liner 1.0 mm (13,2 kg/m2), external cladding 0.75 mm (8,4 kg/m2)
2) System characteristics will be determined based on project specifications

TYPICAL WALL ASSEMBLY DETAILS